Eurocode 7 correlation factors ξ1 to ξ4 for pile resistance

Correlation factor tables for EN 1997-1, the UK and Irish National Annexes and NTC 2018, with worked examples of characteristic pile resistance from load tests.


The correlation factors ξ1 to ξ4 are how Eurocode 7 turns a handful of pile load tests or ground profiles into one characteristic resistance. The rule is the same in both cases: divide the mean result by one factor and the lowest result by another, and take the smaller. More tests or more profiles earn smaller factors. This page gives the tables for EN 1997-1, the UK and Irish National Annexes and NTC 2018, and works through two published examples.

The two rules

static load tests (EN 1997-1 7.6.2.2):
  Rc;k = min( mean(Rc;m) / ξ1 ;  min(Rc;m) / ξ2 )

ground test profiles (EN 1997-1 7.6.2.3):
  Rc;k = min( mean(Rc;cal) / ξ3 ;  min(Rc;cal) / ξ4 )

Rc;m is a measured resistance and Rc;cal is one calculated from a single borehole or CPT, which the Italian code calls an investigated vertical. The mean branch rewards uniform results. The minimum branch protects against one weak location. NTC 2018 writes the same two rules as eqs [6.4.1] to [6.4.4].

ξ1 and ξ2 for static load tests

Number of tests n1234≥ 5
ξ1 (mean), EN 1997-1 Table A.9 and NTC 2018 Tab. 6.4.III1.401.301.201.101.00
ξ2 (minimum), EN 1997-1 and NTC 20181.401.201.051.001.00
ξ1 (mean), UK National Annex1.551.471.421.381.35
ξ2 (minimum), UK National Annex1.551.351.231.151.08

The Irish National Annex load-test factors are not available from a public source, so they are not listed here, and PileCalc does not offer that combination as a preset.

ξ3 and ξ4 for ground test profiles

Number of profiles n123457≥ 10
ξ3, EN 1997-1 Table A.101.401.351.331.311.291.271.25
ξ4, EN 1997-1 Table A.101.401.271.231.201.151.121.08
ξ3, UK National Annex1.551.471.421.381.361.331.30
ξ4, UK National Annex1.551.391.331.291.261.201.15
ξ3, Irish National Annex2.102.032.001.971.941.911.88
ξ4, Irish National Annex2.101.911.851.801.731.681.62
ξ3, NTC 2018 Tab. 6.4.IV1.701.651.601.551.501.451.40
ξ4, NTC 2018 Tab. 6.4.IV1.701.551.481.421.341.281.21

National values differ because the resistance factors that follow them differ. The Irish ξ values are high and its resistance factors are the recommended ones. NTC 2018 pairs its ξ with its own R3 set. Compare whole design chains, not one table against another. The chains are set out for the UK National Annex and for NTC 2018.

Worked example: four static load tests

JRC EUR 26227 example A.8.1 has four static load tests on bored piles with measured resistances of 2.14, 1.96, 1.73 and 2.33 MN.

mean   = (2.14 + 1.96 + 1.73 + 2.33) / 4 = 2.04 MN
lowest = 1.73 MN
n = 4:   ξ1 = 1.10,  ξ2 = 1.00

Rc;k = min( 2.04 / 1.10 ; 1.73 / 1.00 ) = min( 1.85 ; 1.73 ) = 1.73 MN

The lowest test governs. It sits 15 percent below the mean, and with four tests the minimum branch takes over once the lowest is more than 9 percent below (1.00 / 1.10 = 0.91).

Worked example: two static load tests

Example 4 of the ETC10 model solutions (Orr, 2005) has two tests on driven piles, 5000 and 5600 kN.

mean = 5300 kN, lowest = 5000 kN
n = 2:   ξ1 = 1.30,  ξ2 = 1.20

Rc;k = min( 5300 / 1.30 ; 5000 / 1.20 ) = min( 4077 ; 4167 ) = 4077 kN

Here the two tests agree closely and the mean governs. PileCalc's test suite reproduces both examples to the printed digit, in SI and in US units.

When the weakest profile governs

The minimum branch governs when the lowest result divided by the mean is below ξ4 / ξ3 (or ξ2 / ξ1). For the recommended ξ3 and ξ4 that threshold is:

Profiles n23457≥ 10
ξ4 / ξ30.940.920.920.890.880.86

With three boreholes, a weakest profile more than about 8 percent below the mean controls the design. On variable ground, extra investigation lowers ξ but does not lift the weakest profile, so its benefit is smaller than the table suggests. On uniform ground the mean branch governs and going from one profile to ten cuts ξ3 from 1.40 to 1.25, a 12 percent gain in characteristic resistance. Under NTC 2018 the same step is 1.70 to 1.40, a 21 percent gain.

Base and shaft: a gap in the codes

The rules give the total resistance. But a calculation-based design then divides base and shaft by different factors (Rb;k / γb + Rs;k / γs), so the total has to be split, and the codes do not say how when there is more than one profile.

PileCalc keeps both branches. The mean branch divides the mean base and mean shaft by ξ3. The minimum branch divides the base and shaft of the weakest vertical by ξ4. The design resistance is worked out for each and the smaller one is used, with a note in the response. When two verticals tie on total resistance, the one that gives the lower design resistance is taken, so the answer does not depend on the order the boreholes are entered.

Using it in PileCalc

In the axial pile, drilled-shaft and capacity-vs-length tools, choose Calculation on investigated verticals (ξ3, ξ4) as the source of the characteristic resistance and add a soil profile for each borehole or CPT. The tool's method runs on every vertical, and the result names the weakest one, the ξ values and the table column they came from. For static load tests, enter the measured resistances and ξ1 and ξ2 are applied by the number of tests. The procedure around this step is in the Eurocode 7 pile design guide, and the conventions are listed in the design mode docs.

Common questions

What are the correlation factors ξ in Eurocode 7?

They are factors that turn measured or calculated pile resistances into a characteristic resistance. ξ1 and ξ2 apply to static load tests: Rc;k is the lesser of the mean measured resistance over ξ1 and the lowest over ξ2. ξ3 and ξ4 apply to resistances calculated from ground test profiles in the same way. All four fall as the number of tests or profiles grows.

What are the recommended values of ξ3 and ξ4?

In EN 1997-1 Table A.10, ξ3 is 1.40, 1.35, 1.33, 1.31, 1.29, 1.27 and 1.25 for 1, 2, 3, 4, 5, 7 and 10 profiles, and ξ4 is 1.40, 1.27, 1.23, 1.20, 1.15, 1.12 and 1.08. National Annexes change them: the UK starts at 1.55, Ireland at 2.1 and Italy's NTC 2018 at 1.70 for a single profile.

When does the minimum branch govern over the mean?

When the weakest result is far enough below the mean. With the recommended ξ3 and ξ4, the minimum governs once the weakest profile falls below 94 percent of the mean for 2 profiles, 92 percent for 3 or 4, 89 percent for 5 and 86 percent for 10. Uniform ground is governed by the mean, variable ground by its weakest profile.

What if my number of profiles is not in the table?

The tables print ξ3 and ξ4 for 1, 2, 3, 4, 5, 7 and 10 profiles only. For 6, 8 or 9 profiles PileCalc uses the next lower printed count, which is conservative because ξ falls with n, and says so in the response. Engineers who interpolate should record that they did.

Can ξ be reduced for a stiff structure?

Under EN 1997-1 7.6.2.2(9) and 7.6.2.3(7), yes: where the structure is stiff and strong enough to transfer load from weak piles to strong ones, ξ may be divided by 1.1, provided it does not fall below 1.0. The tension clauses have no such allowance, and NTC 2018 has none at all. PileCalc applies it to the compression check only.

Are correlation factors used with the model factor?

No. The model factor belongs to the alternative procedure of EN 1997-1 7.6.2.3(8), where the resistance is calculated once from characteristic ground parameters. That route has no ξ. The ξ3 and ξ4 route calculates a resistance for each profile and applies no model factor.

Sources

EN 1997-1 Tables A.9 and A.10 as reproduced in JRC EUR 26227 (2013), Tables 8.4.1, 8.4.2 and 8.6.1 and example A.8.1; NTC 2018 (D.M. 17 gennaio 2018), Tab. 6.4.III and 6.4.IV; UK National Annex values as reproduced in Raison and Egan (2016); Irish values in Orr (2007); Orr (2005), ETC10 model solutions, Example 4. National Annex values are quoted from public reproductions, not from the annexes themselves. Check them against the documents that govern your project.

Keep reading

Design codes
November 24, 2026

Eurocode 7 pile design: a step-by-step guide (EN 1997-1)

How to design a pile to Eurocode 7: design actions, characteristic resistance from load tests or calculation, Design Approaches, partial factors and a published check.

Read
Design codes
November 24, 2026

Eurocode 7 pile design worked example (DA1, DA2, DA3)

A driven pile in stiff clay sized under all three Design Approaches, following JRC example A.8.2 step by step, with the same case run in PileCalc.

Read
Design codes
November 24, 2026

Eurocode 7 Design Approaches 1, 2 and 3 for piles

DA1, DA2 and DA3 for pile design: the A, M and R factor sets, the recommended resistance factors, which combination governs, and one pile sized under all three.

Read

See it for yourself

Run a laterally loaded pile in your browser — with the deflected shape, moment diagram, and every input explained.

Launch the app