Eurocode 7 pile design worked example (DA1, DA2, DA3)
A driven pile in stiff clay sized under all three Design Approaches, following JRC example A.8.2 step by step, with the same case run in PileCalc.
This Eurocode 7 pile design worked example sizes a driven pile in stiff clay under all three Design Approaches. It is example A.8.2 of the JRC report Eurocode 7: Geotechnical Design. Worked examples (EUR 26227, 2013), a public document, so you can follow every number back to its source. The answer: the same pile needs 12.2 m of shaft in the bearing stratum under DA1, 13.3 m under DA2 and 17.7 m under DA3.
The problem
- Driven pile, diameter D = 0.45 m.
- About 3 m of Brown Dublin Boulder Clay at the top, whose shaft resistance is ignored.
- Black Dublin Boulder Clay below, with a characteristic undrained strength cu;k = 270 kPa.
- Characteristic actions Gk = 600 kN (permanent) and Qk = 300 kN (variable). The example neglects the pile's weight.
- Irish National Annex: the resistance is calculated from characteristic parameters, with a model factor γRd = 1.75.
The unknown is Ls, the length of shaft in the black clay.
Step 1: characteristic resistance
The example takes a unit base resistance of 9 · cu and a unit shaft resistance of α · cu with α = 0.4.
qb;k = 9 · 270 = 2430 kPa Ab = π · 0.45² / 4 = 0.159 m²
qs;k = 0.4 · 270 = 108 kPa perimeter = π · 0.45 = 1.414 m
Rb;k = 2430 · 0.159 = 386 kN
Rs;k = 108 · 1.414 · Ls = 153 · Ls kNThis is the alternative procedure of EN 1997-1 7.6.2.3(8): one calculation on characteristic values, no correlation factor, and a model factor on the resistance factors instead. The other two routes are covered in correlation factors ξ1 to ξ4 explained.
Step 2: design actions
set A1 (DA1 comb. 1, DA2, DA3): Fc;d = 1.35 · 600 + 1.5 · 300 = 1260 kN
set A2 (DA1 comb. 2): Fc;d = 1.0 · 600 + 1.3 · 300 = 990 kNStep 3: design resistance for each approach
For a driven pile the recommended base and shaft factors are equal: 1.0 in R1, 1.3 in R4, 1.1 in R2 and 1.0 in R3. Each is multiplied by the model factor of 1.75.
| Combination | Divisor on Rk | Rc;d (kN) |
|---|---|---|
| DA1 comb. 1 (A1+M1+R1) | 1.0 × 1.75 = 1.75 | 221 + 87.4 · Ls |
| DA1 comb. 2 (A2+M1+R4) | 1.3 × 1.75 = 2.275 | 170 + 67.3 · Ls |
| DA2 (A1+M1+R2) | 1.1 × 1.75 = 1.925 | 201 + 79.5 · Ls |
| DA3 (A1+M2+R3) | 1.0 × 1.75 on cu;d = 270 / 1.4 | 158 + 62.3 · Ls |
DA3 works differently from the others. The strength is factored first, cu;d = 270 / 1.4 = 193 kPa, and the resistance is recalculated from it: Rb = 9 · 193 · 0.159 = 276 kN and Rs = 0.4 · 193 · 1.414 = 109 kN/m, each then divided by 1.75. Note that α stays at 0.4. If it were read again at the lower strength it would rise and cancel part of the factor.
Step 4: solve for the length
DA1 comb. 1: 1260 = 221 + 87.4 · Ls → Ls = 11.9 m
DA1 comb. 2: 990 = 170 + 67.3 · Ls → Ls = 12.2 m (governs DA1)
DA2: 1260 = 201 + 79.5 · Ls → Ls = 13.3 m
DA3: 1260 = 158 + 62.3 · Ls → Ls = 17.7 mAdding the 3 m of upper clay, the pile is about 15.2 m long under DA1, 16.3 m under DA2 and 20.7 m under DA3. The spread between approaches is large here because the whole resistance depends on one strength parameter. Why the approaches differ is the subject of Design Approaches 1, 2 and 3 for piles.
What the numbers mean as a factor of safety
At Ls = 12.2 m the characteristic resistance is 386 + 153 · 12.2 = 2253 kN against an unfactored load of 900 kN, a ratio of 2.5. That matches the product of the DA1 combination 2 factors: 990 / 900 = 1.10 on actions, times 1.3, times 1.75. The partial factors add up to a familiar margin. They only distribute it differently. See partial factors vs a global factor of safety.
The same example in PileCalc
The axial tool takes the example directly. The upper clay is entered with zero strength so that it carries no shaft resistance, the adhesion ratio of the black clay is set to 0.4, and the pile unit weight is zero because the example neglects it. Through the REST API the request body for a 15.5 m pile under DA1 is below. The line of solver settings in the middle controls the mesh and the load-settlement curve, and does not affect the design check.
{
"unitSystem": "si",
"method": "navfac-dm7-reese-oneill",
"pile": { "kind": "uniform", "length": 15.5, "diameter": 0.45,
"elasticModulus": 30000000, "unitWeight": 0, "displacement": true },
"soil": { "layers": [
{ "top": 0, "bottom": 3, "gamma": 20, "type": "cohesive", "cohesion": 0 },
{ "top": 3, "bottom": 40, "gamma": 21, "type": "cohesive", "cohesion": 270, "ka": 0.4 }
] },
"serviceLoad": 300, "segments": 155, "loadSettlementPoints": 60,
"penetrationRatioSide": 20, "penetrationRatioTip": 20, "kDown": 1, "kUp": 1,
"maxTipSettlement": 0.12, "convergenceTolerance": 0.02,
"designBasis": {
"code": "en1997-1-2004",
"nationalAnnex": "ie",
"designApproach": "DA1",
"pileExecution": "driven",
"actions": [
{ "id": "Gk", "kind": "G1", "axialLoad": 600 },
{ "id": "Qk", "kind": "Q", "axialLoad": 300 }
],
"resistance": { "source": "characteristic-parameters" }
}
}The design check in the response gives, for a few lengths:
| Approach | Pile length (Ls) | Combination | Ed (kN) | Rd (kN) | Ed / Rd |
|---|---|---|---|---|---|
| DA1 | 15.0 m (12.0) | 1 | 1260 | 1268 | 0.99 |
| DA1 | 15.0 m (12.0) | 2 | 990 | 975 | 1.02, fails |
| DA1 | 15.5 m (12.5) | 1 | 1260 | 1311 | 0.96 |
| DA1 | 15.5 m (12.5) | 2 | 990 | 1009 | 0.98 |
| DA2 | 16.5 m (13.5) | DA2 | 1260 | 1272 | 0.99 |
| DA3 | 21.0 m (18.0) | DA3 | 1260 | 1279 | 0.98 |
The results bracket the printed lengths: DA1 fails at Ls = 12.0 m and passes at 12.5 m, either side of the published 12.2 m. In the capacity-vs-length tool, a sweep in 0.5 m steps reports 15.5 m as the shortest passing length under DA1 and 16.5 m under DA2. Under the Irish preset with DA3, PileCalc also checks A1+M1+R1, as the Irish National Annex requires in ground of low shear strength. It does not govern here.
Two notes in the response are worth reading. The first says the pile's effective weight is added as a permanent action, which is why the example sets the unit weight to zero to match the source. The second says downdrag is not included in the check.
Try it on your own pile
Replace the two clay layers with your ground model, set the actions and pick the code and Design Approach your project uses. The procedure is laid out in the Eurocode 7 pile design guide, and the options are documented in the design mode docs.
Common questions
Where can I find a worked example of pile design to Eurocode 7?
The European Commission JRC report EUR 26227 (2013), Eurocode 7: Geotechnical Design. Worked examples, is free to download and has pile examples A.8.1 (from static load tests and from a CPT profile) and A.8.2 (from ground parameters, with all three Design Approaches). This page works example A.8.2 step by step.
How long does the pile in JRC example A.8.2 need to be?
The required shaft length in the bearing stratum is 12.2 m under Design Approach 1 (combination 2 governs; combination 1 needs 11.9 m), 13.3 m under Design Approach 2 and 17.7 m under Design Approach 3. The pile also passes through about 3 m of upper clay whose shaft resistance is ignored.
How is the model factor applied in the example?
The resistance is calculated from characteristic ground parameters, which is the alternative procedure of EN 1997-1 7.6.2.3(8). The Irish National Annex model factor of 1.75 multiplies the base and shaft resistance factors, so under DA1 combination 2 the base resistance is divided by 1.3 × 1.75 = 2.275.
Why does Design Approach 3 need the longest pile?
DA3 divides the undrained strength by 1.4 before the resistance is calculated and keeps the resistance factor at 1.0. In this example α is held constant, so the shaft and base resistances both fall by the full 1.4, which is more than the 1.1 of DA2 or the 1.3 of DA1 combination 2 (the latter paired with smaller action factors).
Does PileCalc reproduce this example?
Yes. PileCalc's test suite runs example A.8.2 through the axial tool in SI and US units and matches the printed design actions, the base and shaft terms of every combination, and the required lengths within the rounding of the source. The capacity-vs-length tool returns the shortest swept length that passes.
Sources
Bond, Schuppener, Scarpelli and Orr (2013), Eurocode 7: Geotechnical Design. Worked examples, JRC EUR 26227 EN, example A.8.2, pp. 156 to 160. The PileCalc rows are output of the current engine. They are a reproduction of a published example, not a design. Results remain the engineer's responsibility to review.
Keep reading
Eurocode 7 pile design: a step-by-step guide (EN 1997-1)
How to design a pile to Eurocode 7: design actions, characteristic resistance from load tests or calculation, Design Approaches, partial factors and a published check.
ReadEurocode 7 Design Approaches 1, 2 and 3 for piles
DA1, DA2 and DA3 for pile design: the A, M and R factor sets, the recommended resistance factors, which combination governs, and one pile sized under all three.
ReadEurocode 7 correlation factors ξ1 to ξ4 for pile resistance
Correlation factor tables for EN 1997-1, the UK and Irish National Annexes and NTC 2018, with worked examples of characteristic pile resistance from load tests.