Pile design from CPT to Eurocode 7 (EN 1997-2 Annex D)
EN 1997-2 Tables D.3 and D.4 for bored piles in coarse soil: unit shaft and base resistance from cone resistance, with a worked example from one CPT profile.
Eurocode 7 lets you calculate pile resistance straight from a cone penetration test. EN 1997-2 Annex D gives an example correlation for bored piles in coarse soil: Table D.4 turns the cone resistance qc into a unit shaft resistance and Table D.3 turns it into a unit base resistance. The resistance calculated on each CPT profile then becomes a characteristic value through the correlation factors ξ3 and ξ4. This page gives both tables and works a published example end to end.
Table D.4: unit shaft resistance
| Cone resistance qc (MPa) | 0 | 5 | 10 | ≥ 15 |
|---|---|---|---|---|
| Unit shaft resistance ps (MPa) | 0 | 0.04 | 0.08 | 0.12 |
Intermediate values are interpolated linearly. In effect ps is 0.8 percent of qc, capped at 0.12 MPa once qc reaches 15 MPa.
Table D.3: unit base resistance
| Normalised settlement s/D | qc = 10 MPa | qc = 15 MPa | qc = 20 MPa | qc = 25 MPa |
|---|---|---|---|---|
| 0.02 | 0.70 | 1.05 | 1.40 | 1.75 |
| 0.03 | 0.90 | 1.35 | 1.80 | 2.25 |
| 0.10 (ultimate) | 2.00 | 3.00 | 3.50 | 4.00 |
Values are the unit base resistance pb in MPa, again with linear interpolation. The ultimate limit state uses the row at s/D = 0.10, a settlement of one tenth of the base diameter. The table stops at 10 and 25 MPa and prints nothing outside that range. For a cast in-situ pile with an enlarged base, the values are multiplied by 0.75.
The rows tell a useful story about bored piles. At a settlement of 2 percent of the diameter only 35 to 44 percent of the ultimate base resistance is mobilised. The shaft mobilises at much smaller movement, which is one reason base resistance carries higher partial factors and why the split between skin friction and end bearing matters for serviceability.
Worked example: bored pile from one CPT profile
JRC EUR 26227 example A.8.1(b) designs a bored pile of diameter 0.45 m. Loose sand, soft clay and peat extend to 16.5 m and are given no shaft resistance. The dense sand below has qc = 12.5 MPa. The pile carries Gk = 300 kN and Qk = 150 kN, and there is one CPT profile.
Unit and calculated resistances
qc = 12.5 MPa, halfway between the 10 and 15 MPa columns:
pb = (2.0 + 3.0) / 2 = 2.5 MPa (Table D.3, s/D = 0.10)
ps = (0.08 + 0.12) / 2 = 0.10 MPa (Table D.4)
Rb;cal = 2500 · π · 0.45² / 4 = 398 kN
Rs;cal = 100 · π · 0.45 · Ls = 141 · Ls kN (Ls = length in the dense sand)Characteristic resistance
one profile: ξ3 = ξ4 = 1.40
Rb;k = 398 / 1.40 = 284 kN
Rs;k = 141 · Ls / 1.40 = 101 · Ls kNDesign check and length
DA1 comb. 1: Fc;d = 1.35·300 + 1.5·150 = 630 kN
630 = 284 / 1.25 + 101 · Ls / 1.0 → Ls = 3.99 m
DA1 comb. 2: Fc;d = 1.0·300 + 1.3·150 = 495 kN
495 = 284 / 1.6 + 101 · Ls / 1.3 → Ls = 4.09 m
DA2: Fc;d = 630 kN
630 = 284 / 1.1 + 101 · Ls / 1.1 → Ls = 4.05 mThe pile needs about 4.1 m in the dense sand, so 21 m overall. The three checks land within 10 cm of each other. One detail for anyone checking against the source: the report prints 4.08 m for DA1 combination 2, but its own equation gives 4.09 m. PileCalc reproduces the equation, and its test suite records the difference.
More than one CPT
With several profiles, the calculation is repeated on each and the characteristic resistance is the lesser of the mean over ξ3 and the lowest over ξ4. Two CPTs lower ξ3 from 1.40 to 1.35 and ξ4 to 1.27; five give 1.29 and 1.15. Each sounding is cheap next to a pile, so the extra profiles usually pay for themselves on uniform ground. The tables and the rule for when the weakest profile governs are in correlation factors ξ1 to ξ4 explained.
Limits of the tables
- They are for bored piles. Driven piles need a different method.
- They are for coarse soil. Clay and silt layers are outside them.
- The base table covers qc from 10 to 25 MPa only and prints nothing outside that range.
- Annex D is informative and calls the tables an example. EN 1997-2 attaches conditions of application to them, and a National Annex may point to another method. Read both before relying on the numbers.
- qc is an average over a zone, chosen cautiously. Choosing it is engineering judgement that no table replaces.
CPT-based resistance in PileCalc
In the axial pile and capacity-vs-length tools, a coarse (cohesionless) layer can carry a CPT cone resistance in place of the NAVFAC DM-7.02 values. For a bored pile the unit shaft resistance is then read from Table D.4 and, where the tip bears in the layer, the unit base resistance from Table D.3 at s/D = 0.10. Other layers keep the tool's method or take unit resistances you enter. The response notes every layer whose resistance did not come from NAVFAC.
What the tool checks and what it leaves to you:
- A cone resistance on a driven pile or a fine-grained layer is rejected, and so is a tip cone resistance outside 10 to 25 MPa.
- An enlarged base takes 0.75 of the Table D.3 value.
- The toe load-settlement curve of a cone-bearing tip follows the Table D.3 ratios at s/D of 0.02, 0.03 and 0.10. Below 0.02 the table is silent and a straight line from the origin is assumed, which is stated in the response.
- The same shaft value is used in uplift, with the tension factor in design mode. The table is for compression, so the response flags this.
- The other conditions of application in EN 1997-2 Annex D are not checked. The drilled-shaft tool does not take cone resistance.
With limit-state design switched on, add a soil profile per CPT and the check applies ξ3 and ξ4 across them. The procedure is in the Eurocode 7 pile design guide and the inputs are documented under entered and CPT unit resistances.
Common questions
How do you get pile resistance from CPT results in Eurocode 7?
EN 1997-2 Annex D gives an example correlation for bored piles in coarse soil. Table D.4 gives the unit shaft resistance from the cone resistance qc, and Table D.3 gives the unit base resistance from the average qc near the pile base and the normalised settlement s/D. The calculated resistance of each CPT profile is then divided by the correlation factors ξ3 and ξ4 to give the characteristic resistance.
What unit shaft resistance does EN 1997-2 Table D.4 give?
0.04 MPa at qc = 5 MPa, 0.08 MPa at 10 MPa and 0.12 MPa at 15 MPa or more, with linear interpolation between them and zero at qc = 0. That is 0.8 percent of qc up to 15 MPa, capped at 120 kPa.
What unit base resistance does EN 1997-2 Table D.3 give at failure?
At a normalised settlement s/D of 0.10, which is taken as the ultimate state: 2.0 MPa at qc = 10 MPa, 3.0 MPa at 15 MPa, 3.5 MPa at 20 MPa and 4.0 MPa at 25 MPa. The table also gives values at s/D of 0.02 and 0.03. A cast in-situ pile with an enlarged base takes 0.75 of the tabulated value.
Do the EN 1997-2 CPT tables apply to driven piles?
No. Tables D.3 and D.4 are for bored piles in coarse soil. PileCalc rejects a cone resistance input for a driven pile or a fine-grained layer. For those cases, enter unit shaft and base resistances from a method that suits the pile and the ground.
Can PileCalc design a pile directly from CPT data?
For bored piles in coarse layers, yes: enter the layer's cautious average cone resistance in the axial pile or capacity-vs-length tool and the unit resistances are read from EN 1997-2 Tables D.3 and D.4. The cone resistance at the pile tip must be between 10 and 25 MPa. PileCalc does not import a CPT sounding file or average the trace for you.
Sources
EN 1997-2 Tables D.3 and D.4 as reproduced in JRC EUR 26227 (2013), Eurocode 7: Geotechnical Design. Worked examples, Tables A.5.6, A.5.7, A.8.1 and A.8.2, and example A.8.1(b), pp. 152 to 155. The tables are quoted from that public reproduction. Check them against EN 1997-2 and your National Annex.
Keep reading
Eurocode 7 pile design: a step-by-step guide (EN 1997-1)
How to design a pile to Eurocode 7: design actions, characteristic resistance from load tests or calculation, Design Approaches, partial factors and a published check.
ReadEurocode 7 pile design worked example (DA1, DA2, DA3)
A driven pile in stiff clay sized under all three Design Approaches, following JRC example A.8.2 step by step, with the same case run in PileCalc.